Most induction motors are started directly on line, but when very large motors are started that way, they cause a disturbance of voltage on the supply lines due to large starting current surges. To limit the starting current surge, large induction motors are started at reduced voltage and then have full supply voltage reconnected when they run up to near rotated speed.

Two methods used for reduction of starting voltage are: Star delta Starting and Auto transformer starting.

The Star/Delta starter is manufactured from three contactors, a timer and a thermal overload. The contactors are smaller than the single contactor used in a Direct on Line starter as they are controlling winding currents only. The currents through the winding are 1/root 3 (58%) of the current in the line.

  • Features of star-delta starting
  • For low- to high-power three-phase motors.
  • Reduced starting current
  • Six connection cables
  • Reduced starting torque
  • Current peak on changeover from star to delta
  • Mechanical load on changeover from star to delta

Application of Star-Delta Starter

The star-delta method is usually only applied to low to medium voltage and light starting Torque motors.

The received starting current is about 30 % of the starting current during direct on line start and the starting torque is reduced to about 25 % of the torque available at a D.O.L start. This starting method only works when the application is light loaded during the start.

If the motor is too heavily loaded, there will not be enough torque to accelerate the motor up to speed before switching over to the delta position.